Add to Cart
H05V-U PVC Electrical Cable 300/500 V Single Core Solid Conductor Wire
Application
Insulated conductor for internal wiring of electrical devices and lighting fixtures, i.e. as bridge junction. Laying in dry areas, in switchboards and distribution boards. In electrical-installation canal which can be opened, only for signaling and control circuits. Not for direct application under plaster.
Standards
HRN HD 21.3 S3
IEC 60227-3
DIN VDE 0281 part 3
Construction
Conductor:bare copper conductor of class 1 (solid) acc, to IEC 60228 / HD 383 / DIN VDE 0295
Insulation:PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3
Insulation colors:
Temperature range:
During installation:+5 °C up to+70 °C
Fixed installed:-30 °C up to+70 °C
At short circuit of max. 5 s:up to 160 °C
Ambient temperature at storage:up to 40 °C
Nominal voltage:Uο/U = 300/500 V
Test voltage:2000 V
Minimal inner bending radius:4D
Behavior in fire:IEC 60332-1
Dimensions – conductor cross-section | Construction of individual conductor | External diameter | Insulation thickness | Conductor resistance at 20 °C | Specific. el. resistance of insulation at 70°C | Cu weight | Cable weight | Permitted stress | Packing* |
nominal | min-max. | nominal | max. | min. | approx. | max. | |||
mm² | n x mm | mm | mm | Ω/km | MΩkm | kg/km | kg/km | N | |
0,5 | 1 x 0,80 | 1,9 – 2,3 | 0,6 | 36,0 | 0,014 | 4,8 | 9 | 25 | c.100 |
0,75 | 1 x 0,95 | 2,1 – 2,5 | 0,6 | 24,5 | 0,013 | 7,2 | 10 | 37,5 | c.100 |
1 | 1 x 1,13 | 2,2 – 2,7 | 0,6 | 18,1 | 0,011 | 9,6 | 14 | 50 | c.100 |
*) Packing: c.100 = coil 100 m