H05V2V2-F PVC Electrical Cable Heat Resistant Flexible Copper Conductor Cable
APPLICATION
H05V2V2-F Heat resistant cables suitable for uses in domestic environments, kitchen, offices, as well as power supply cords of household appliances that are undergone by medium mechanical abuses (washing-machines, hair-dryers, refrigerators). Also, they can be used for heating devices provided they are not in direct touch with hot surfaces or exposed to thermal irradiation. They are not suitable for outdoor use, industrial or agricultural workshops and non-domestic devices.
CONSTRUCTION
Conductor
Insulation
Sheath
CABLE STANDARDS
BS EN 50525-2-11 (previously BS 6500, BS 7919 table 41),
BS EN/IEC 60332-1-2
DIMENSIONS
UNIQUE PART NO. | NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL THICKNESS OF INSULATION | NOMINAL THICKNESS OF SHEATH | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT |
mm² | mm | mm | mm | kg/km | ||
H05V2V2-F2X0.75 | 2 | 0.75 | 0.6 | 0.8 | 6.3 | 63 |
H05V2V2-F3X0.75 | 3 | 0.75 | 0.6 | 0.8 | 6.7 | 74 |
H05V2V2-F3X1 | 3 | 1 | 0.6 | 0.8 | 7 | 86 |
H05V2V2-F3X1.5 | 3 | 1.5 | 0.7 | 0.9 | 8.1 | 115 |
H05V2V2-F3X2.5 | 3 | 2.5 | 0.8 | 1 | 9.7 | 170 |
H05V2V2-F4X0.75 | 4 | 0.75 | 0.6 | 0.8 | 7.3 | 78 |
H05V2V2-F4X1 | 4 | 1 | 0.6 | 0.9 | 7.9 | 110 |
H05V2V2-F4X1.5 | 4 | 1.5 | 0.7 | 1 | 9 | 140 |
H05V2V2-F4X2.5 | 4 | 2.5 | 0.8 | 1.1 | 10.8 | 210 |
H05V2V2-FX0.75 | 5 | 0.75 | 0.6 | 0.9 | 8.1 | 105 |
CONDUCTORS
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² | MAXIMUM DIAMETER OF WIRES IN CONDUCTOR mm | MAXIMUM RESISTANCE OF CONDUCTOR AT 20oC | |
Plain Wires ohms/km | Metal-Coated Wires ohms/km | ||
0.75 | 0.21 | 26 | 26.7 |
1 | 0.21 | 19.5 | 20 |
1.5 | 0.26 | 13.3 | 13.7 |
2.5 | 0.26 | 7.98 | 8.21 |
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity and Mass Supportable
NOMINAL CROSS SECTIONAL AREA mm2 | CURRENT CARRYING CAPACITY | MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CORD | |
Single-Phase AC Amps | Three-Phase AC Amps | ||
0.75 | 6 | 6 | 3 |
1 | 10 | 10 | 5 |
1.5 | 16 | 16 | 5 |
2.5 | 25 | 20 | 5 |
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm2 | DC OR SINGLE-PHASE AC mV/A/m | THREE-PHASE AC mV/A/m |
0.75 | 62 | 54 |
1 | 46 | 40 |
1.5 | 32 | 27 |
2.5 | 19 | 16 |