VDE 0482-332-1-2 Standard Flexible Control Cable VFD EMC 2YSLCY Cable
APPLICATION
The cable has been developed for connecting motors to inverse rectifiers under consideration of EMC (electromagnetic compatibility) requirements. It may be used under medium mechanical stress for fixed installations and temporary movement. This cable offers a good resistance against oil and grease. Suitable for outdoor installation but not direct burial.
CABLE STANDARDS
VDE 0482-332-1-2, BS EN/IEC 60332-1, BS EN/IEC 60811-2,
BS EN 60228
DIMENSIONS
UNI-Cables PART NO. | NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | |
Power Conductor | Earth Conductor | mm | kg/km | ||
UNIVFD03015 | 3 + 3 earth | 1.5 | 0.25 | 10.2 | 140 |
UNIVFD03025 | 3 + 3 earth | 2.5 | 0.5 | 11.4 | 220 |
UNIVFD03040 | 3 + 3 earth | 4 | 0.75 | 13.1 | 323 |
UNIVFD03060 | 3 + 3 earth | 6 | 1 | 14.9 | 420 |
UNIVFD0310 | 3 + 3 earth | 10 | 1.5 | 18.4 | 615 |
UNIVFD0316 | 3 + 3 earth | 16 | 2.5 | 21.6 | 819 |
UNIVFD0325 | 3 + 3 earth | 25 | 4 | 25.3 | 1402 |
UNIVFD0335 | 3 + 3 earth | 35 | 6 | 27.8 | 1718 |
UNIVFD0350 | 3 + 3 earth | 50 | 10 | 32.6 | 2399 |
UNIVFD0370 | 3 + 3 earth | 70 | 10 | 38.9 | 3173 |
UNIVFD0395 | 3 + 3 earth | 95 | 16 | 44.3 | 4162 |
UNIVFD03120 | 3 + 3 earth | 120 | 16 | 46.8 | 5253 |
UNIVFD03150 | 3 + 3 earth | 150 | 25 | 53.5 | 6128 |
UNIVFD03185 | 3 + 3 earth | 185 | 35 | 59.5 | 7450 |
UNIVFD03240 | 3 + 3 earth | 240 | 50 | 70 | 10800 |
UNIVFD04015 | 4 | 1.5 | - | 10.4 | 154 |
UNIVFD04025 | 4 | 2.5 | - | 12.3 | 229 |
UNIVFD04040 | 4 | 4 | - | 14.5 | 339 |
UNIVFD04060 | 4 | 6 | - | 16.8 | 451 |
UNIVFD0410 | 4 | 10 | - | 19.7 | 667 |
UNIVFD0416 | 4 | 16 | - | 22 | 892 |
UNIVFD0425 | 4 | 25 | - | 27 | 1440 |
UNIVFD0435 | 4 | 35 | - | 30.3 | 1861 |
UNIVFD0450 | 4 | 50 | - | 35 | 2547 |
UNIVFD0470 | 4 | 70 | - | 39.4 | 3404 |
UNIVFD0495 | 4 | 95 | - | 46 | 4888 |
UNIVFD04120 | 4 | 120 | - | 51.4 | 5703 |
UNIVFD04150 | 4 | 150 | - | 58.8 | 7040 |
UNIVFD04185 | 4 | 185 | - | 61.1 | 9150 |
UNIVFD04240 | 4 | 240 | - | 70 | 12500 |
CONDUCTORS
NOMINAL CROSS SECTIONAL AREA | MAXIMUM DIAMETER OF WIRES IN CONDUCTOR | MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C |
mm² | mm | ohms/km |
1.5 | 0.26 | 13.3 |
2.5 | 0.26 | 7.98 |
4 | 0.31 | 4.95 |
6 | 0.31 | 3.3 |
10 | 0.41 | 1.91 |
16 | 0.41 | 7.98 |
25 | 0.41 | 4.95 |
35 | 0.41 | 0.554 |
50 | 0.41 | 0.386 |
70 | 0.51 | 0.272 |
95 | 0.51 | 0.206 |
120 | 0.51 | 0.161 |
150 | 0.51 | 0.129 |
185 | 0.51 | 0.106 |
240 | 0.51 | 0.0801 |
300 | 0.51 | 0.0641 |
ELECTRICAL CHARACTERISTICS
NOMINAL CROSS SECTIONAL AREA mm² | CURRENT CARRYING CAPACITY IN AIR Amps |
1.5 | 18 |
2.5 | 26 |
4 | 34 |
6 | 44 |
10 | 61 |
16 | 82 |
25 | 108 |
35 | 135 |
50 | 168 |
70 | 207 |
95 | 250 |
120 | 292 |
150 | 335 |
185 | 382 |
240 | 453 |
300 | 523 |