BS EN60702 Fire Proof Cable 2 Cores Mineral Insulated Heavy Duty 750V

Ask Latest Price
Brand Name :UNI-CABLES
Model Number :MIC Heavy Duty
Certification :ISO9001
Place of Origin :CHINA
MOQ :1000 Meters
Price :Depends on Quantity
Supply Ability :10000 Meters per Week
Delivery Time :15-20 working days
Packaging Details :5 Meters or 11 Meters
Voltage Rating (Uo/U) :750V
Temperature Rating :-10°C to 250°C
Sheath Colour :Red White Orange
Conductor :Solid plain copper conductor
Insulation :Magnesium Oxide
Sheath :Copper tube, LSZH (Low Smoke Zero Halogen)
Contact Now

Add to Cart

Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
View Product Description

BS EN60702 Fire Resistance Cable 2 Cores Mineral Insulated Heavy Duty 750V

APPLICATION

A 750V heavy duty mineral insulated cable, designed to give the ultimate Fire Performance.

Suitable for Oil, Gas and Petroleum industries, airports, emergency lighting systems and fire alarm systems for power and control circuits providing circuit integrity to 950°C.

Construction Solid copper conductor. Compressed magnesium oxide powder insulation. Solid copper sheath.
Operating Temperature -10degC to +250degC
Minimum Bending Radius 6 x overall diameter
Core Identification Coloured sleeving available
Lengths 100/500m. Special lengths available on request.
Sheath Colour N/A
Manufacturing Standard BS EN 60702-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2e Enhanced
BS 5266
BS 8519 Category 1 & 2 Control
(for Category 3 & power applications see special notes)
Fire Tests BS 8434-2
BS EN 50200 PH30, PH60, PH120
BS 6387 C W & Z
BS 8491
Emissions and
Flame Propagation
In its bare form there are no emissions

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm²
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
2 1 6.4 126
2 1.5 7 154
2 2.5 7.9 206
2 4 9.2 322
3 1 7.1 159
3 1.5 7.7 194
3 2.5 8.8 272
4 1 7.6 187
4 1.5 8.3 231
4 2.5 9.6 336
7 1.5 9.9 351
7 2.5 11.2 475

CONDUCTOR

NOMINAL CROSS SECTIONAL AREA MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
mm² ohms/km
1 18.1
1.5 12.1
2.5 7.41
4 4.61

ELECTRICAL CHARACTERISTICS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm²
SINGLE PHASE AC OR DC
Amps
THREE PHASE AC
Amps
2 1 18.5 -
2 1.5 23 -
2 2.5 31 -
2 4 40 -
3 1 - 15
3 1.5 - 19
3 2.5 - 26
4 1 - 15
4 1.5 - 19
4 2.5 - 26
7 1.5 13 -
7 2.5 17.5 -

Voltage Drop

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm²
SINGLE PHASE AC OR DC
mV/A/M
THREE PHASE AC
mV/A/M
2 1 42 -
2 1.5 28 -
2 2.5 17 -
2 4 10 -
3 1 - 36
3 1.5 - 24
3 2.5 - 14
4 1 - 36
4 1.5 - 24
4 2.5 - 14
7 1.5 28 -
7 2.5 17 -